KGC-11/24 series SF6 gas insulated ring main unit

The KGC series SF6 gas fully insulated compact ring main unit (RMU) is a new type of medium-voltage switchgear with SF6 gas insulation independently developed by Mojuu Company. The product adopts a modular design and can be arbitrarily arranged according to different design schemes, achieving a perfect combination of a common box unit and an expandable unit to meet the flexible use requirements of various secondary transmission and distribution substations for compact switchgear.

The KGC series switchgear is a completely sealed system. All its primary components are enclosed in a stainless-steel housing and are not affected by the environment. It has the characteristics of reliable operation, safety assurance, compact structure design, small space occupation, maintenance-free, and long service life.

The product has passed the type test at the national high-voltage electrical appliance test center and is widely used in small secondary substations, box-type switch stations, industrial and mining enterprises, airports, railways, commercial areas, high-rise buildings, expressways, subways, tunnels, and places with harsh natural conditions.

  • Product Details

Execution Standards

GB/T3804 3.6kV - 40.5kV High - voltage Alternating - current Load Switches

GB/T1984 High - voltage Alternating - current Circuit - breakers

GB/T16926 High - voltage Alternating - current Load Switch - Fuse Combinations

GB/T1985 High - voltage Alternating - current Disconnectors and Earthing Switches

GB/T3906 3.6kV - 40.5kV AC Metal - enclosed Switchgear and Controlgear

GB/T11022 Common Technical Requirements for High - voltage Switchgear and Controlgear Standards

GB/T4208 Degrees of Protection Provided by Enclosures (IP Code)

DL/T404 3.6kV - 40.5kV AC Metal - enclosed Switchgear and Controlgear

GB/T311.1 Insulation Coordination - Part 1: Definitions, Principles and Rules

Standardized Design and Customization Scheme for 11kV Ring - main Unit (Cabinet) (2022 Edition)


Main Technical Parameter Table of KGC-11kV/630A Ring Main Unit

Serial number

Project

unit

Load switch unit

Combined electrical apparatus unit

Circuit breaker unit

Rated voltage

kV

11 

11

11

Rated frequency

Hz

50

50

50


3

Rated current

A

630

125 (depending on the fuse current)

630


4

Rated

Insulation

Level

1min Power Frequency Withstand Voltage

Interphase, to ground

kV

42

42

42

fracture surface

kV

48

48

48

Control and auxiliary circuits

kV

2

2

2

Lightning impulse withstand voltage

Interphase, to ground

kV

75

75

75

fracture surface

kV

85

85

85

Rated short-time withstand current

kA/s

20、25/4

——

20、25/4

 Rated peak withstand current

kA

50、63

——

50、63

Rated short - circuit breaking current

kA

——

Limited by the high-voltage fuse

20、25

Rated short - circuit making current

kA

50、63

Limited by the high-voltage fuse

50、63

Rated transfer current

A

——

1700 

——

10 

Rated active load breaking current

A

630 

——

——

11

Rated closed-loop breaking current

A

630 

——

——

12

Rated operating sequence

/

——

——

O-0.3s-CO-180s-CO

13 

Mechanical life

Load switch/Circuit breaker

times

10000

10000

20000

Isolation/Earthing Switch

times

3000

3000

3000

14 

Loop resistance

μΩ

≤150

——

≤150

15 

Rated inflation pressure (gauge pressure at 20℃)

MPa

0.04

16 

Annual relative gas leakage rate

year

≤0.01%

17

Insulating gas


SF6

18

Protection level

Compartment (IP code)

/

IP2XC

Gas tank (IP code)

/

IP67

Cabinet (IP code)

/

IP41

Cabinet (IK code)

/

IK10

19 

Arc ignition test (fault current / duration)

kA/s

20/1、25/0.5

 

Main Technical Parameter Table of KGC-24kV/630A Ring Main Unit

Serial number

Project

unit

Load switch unit

Combined electrical apparatus unit

Circuit breaker unit

Rated voltage

kV

24 

24 

24 

Rated frequency

Hz

50 

50 

50 

3

Rated current

A

630 

125 (depending on the fuse current)

630 

4

Rated

Insulation

Level

1min Power Frequency Withstand Voltage

Interphase, to ground

kV

65 

65 

65 

fracture surface

kV

79 

79 

79 

Control and auxiliary circuits

kV

Lightning impulse withstand voltage

Interphase, to ground

kV

125 

125 

125 

fracture surface

kV

145 

145 

145 

Rated short-time withstand current

kA/s

20、25/4

——

20、25/4

Rated peak withstand current

kA

50、63

——

50、63

Rated short - circuit breaking current

kA

——

Limited by high-voltage fuses

20、25

Rated short - circuit making current

kA

50、63

Limited by high-voltage fuses

50、63

Rated transfer current

A

    ——

1400 

——

  10 

Rated active load breaking current

A

630 

——

——

  11 

Rated closed-loop breaking current

A

630 

——

——

  12 

Rated operating sequence

/

——

——

O-0.3s-CO-180s-CO

  13 

Mechanical life

Load switch/Circuit breaker

times

5000 

5000 

10000 

Isolation/Earthing Switch

times

3000 

3000 

3000 

  14 

Loop resistance

μΩ

≤150

——

≤150

  15 

Rated inflation pressure (gauge pressure at 20℃)

MPa

0.04 

  16 

Annual relative gas leakage rate

 year

≤0.01%

  17 

Insulating gas


SF6

18

Protection level

Compartment (IP code)

/

IP2XC

Gas tank (IP code)

 /

IP67

Cabinet (IP code)

 /

IP41

Cabinet (IK code)

/

IK10

 

Main Technical Parameter Table of KGC-11kV/1250A Ring Main Unit

Serial number

Project

unit

Circuit breaker unit

1

Rated voltage

kV

11 

2

Rated frequency

Hz

50 

Rated current

A

1250 

Rated

Insulation

Level

1min Power Frequency Withstand Voltage

Interphase, to ground

kV

42 

fracture surface

kV

48 

Control and auxiliary circuits

kV

Lightning impulse withstand voltage

Interphase, to ground

kV

75 

fracture surface

kV

85 

5

Rated short-time withstand current

kA/s

25、31.5/4

6

Determine the peak withstand current

kA

6,380

7

Rated short - circuit breaking current

kA

25、31.5

Rated short - circuit making current

kA

63、80

Rated transfer current

/

0-0.3s-CO-180s-CO

10 

Mechanical life

Load switch circuit breaker

times

10000 

Isolation/Earthing Switch

times

3000 

11

Loop resistance

μΩ

≤150

12 

Rated inflation pressure (gauge pressure at 20℃)

MPa

    0.04

13

Annual relative gas leakage rate

year

    ≤0.01%

14

Insulating gas

/

    SF6

15

Protection level

Compartment (IP code)

/

    IP2XC

Gas tank (IP code)

/

    IP67

ACabinet (P code)

/

    IP41

Cabinet (IK code)

/

    IK10

16

Arc ignition test (fault current / duration time)

    kA/s

31.5/0.5


Installation Dimension Table

The cabinet depth of the 11kV standard complete machine is 750mm, and the cabinet height is 1450mm (without instrument box). The optional heights of the instrument box are 200mm, 350mm, and 470mm.

Number of common box units

1

2

3

4

5

6

Net width of the air box

325

650

975

1300

1625

1950

Note: The total width of the cabinet is determined by the end panel matched with the user's plan.

In addition, according to the user's needs, cabinet types with standardized dimensions of the State Grid can be provided.