The KYV-11/630-20/25 high-voltage switch body is a vacuum circuit breaker dedicated to 11kV SF6 gas-insulated switchgear. The switch adopts a clamping plate structure and has advantages such as reliable breaking performance, long service life, maintenance-free, and convenient installation.
The KYV-11/630-20/25 vacuum circuit breaker is applied to the KGC-11(V)/630-20/25 type gas-insulated switchgear or other similar types of SF6 gas-insulated switchgear. As a main component of the gas-insulated switchgear, it has the performance of switching rated current and load current, closing and breaking short-circuit current.
Use of environmental conditions
Environmental temperature: Maximum temperature: +50℃; Minimum temperature: -40℃;
Environmental humidity: The average relative humidity within 24 hours does not exceed 95%; the average monthly relative humidity does not exceed 90%;
Installation environment: The surrounding air has no explosive and corrosive gases, and the installation site has no severe vibration and shock;
Seismic intensity: 9 degrees;
Rated relative pressure of SF6 gas: 0.04MPa. The SF6 gas complies with the requirements of GB/T12022 - 2014 "Industrial Sulfur Hexafluoride".
Main technical parameters
Serial number | project | unit | parameters | Remarks |
1 | Rated voltage | kV | 11 | |
2 | Rated frequency | Hz | 50 | |
3 | Rated current | A | 630 | |
4 | Rated short-time withstand current | kA/s | 20/4、25/4 | |
5 | Rated peak withstand current | kA | 50/63 | |
6 | Rated short - circuit breaking current | kA | 50/63 | |
7 | Rated short - circuit making current | kA | 50/63 | |
8 | Rated cable charging breaking current | A | 20/25 | |
9 | Number of short - circuit current breaking times | times | 30 | |
10 | 1min power frequency withstand voltage | kV | 42/48 | In SF6 gas |
11 | Lightning impulse withstand voltage | kV | 75/85 | |
12 | Mechanical life | times | 20000 | |
13 | Main circuit resistance | μΩ | ≤65 | Add isolating switch |
14 | Interphase center distance | mm | 150 |
Technical requirements:
1. The total stroke of the vacuum circuit breaker is 11 ± 1mm, and the over-travel is 2.5 ± 0.5mm;
2. The contact pressure of the moving contact of the three-position switch is 260 ± 20N (internally controlled at 260 + 10N) and it has an adjustable structure.